TENSE HSR-02 Hydrophore Sequencing Relays
General :
Hydrophore Sequencing Relays have been designed as they
will start operating when needed and operate simultaneously
Hydrophore sequencing relays are designed to regulate the number of booster that should operate according to the pressure and to ensure that the booster operates in equal time.
2x Pressure Switch Inputs
2x Hydrophore Outputs
Usage of Device and Working Principle
The hydrophore sequence is as follows: (H1) - (H2) - (H3) and (H1-H2) -
(H2-H3) - (H1-H3). It activates hydrophores at the same
number with the
closed switches and keeps them operating during the
"t" time. After the
"t" time is up, it engages the next hydrophore or
the hydrophore group and
t continues in this way. It deactivates hydrophores at the
same number
with the open switches.
Note: Do not energize
the inputs and outputs (P1, P2, P3)
of the pressure switch.
Maintenance :
Switch off the device and release from connections. Clean the trunk
of device with a swab. Don’t use any conductor or chemical might
damage the device. Make sure device works after cleaning
Warnings :
Please use the device according to the manual. Don’t use the device in wet. Include a switch and circuit breaker in the assembly. Put the switch and circuit breaker nearby the device, operator can reach easily. Mark the switch and circuit breaker as releasing connection for device
Tecnical
Specifications:
Operating Voltage(Un): 150-250V AC
Operating
Frequency: 50/60 Hz
Operating Power: <6VA
Operating Temperature: -20°C.... +55°C
Time(t): 10minutes
Display: HSR-02=5
x led, HSR-03=7 x led
Connection Type: Terminal connection
Cable Diameter: 1.5mm²(HSR-02), 2.5mm²(HSR-03)
Number Hydrophore: 2(HSR-02) and 3(HSR-03)
Number Pressure Switch: 2(HSR-02) and 3(HSR-03)
Contact: 3A/250V AC (Resistive Load)
Operating Altitude: <2000meter
Mounting: Vertical assembled in the panel
or assembled on the din rail.
Downlaod PDF manual
- Stock: Out Of Stock
- Model: HSR-02